A comprehensive range of conventional detectors are available to operate with the Cooper conventional panel range.
Benefits and Features
- LPCB 3rd party approved / CPD approved
- Low profile design
- 360° viewable LED design
- Removable detector chamber for cleaning
- Common mounting base
- New enhanced detectors feature Dual LEDs,
- Drift compensation and Chamber monitoring (Optical & Photo-Thermal)
Model (UNB)
CPD321
CPT341
CFR330
CMT360
CHT390
Description
Optical Sensor
Photo-Themal Sensor
Heat Sensor (Fast)
Heat Sensor (Med)
Heat Sensor (High)
CPD approved product
0832CPD0633
0832CPD0629
0832CPD0233
0832CPD0236
0832CPD0237
Standards
EN54 pt7:2000
EN54 pt7:2000
EN54 pt5:2000 + A1:2002
+ A1:2002
+ A1:2002
EN54 pt5:2000
+ A1:2002
Area coverage
100m² (subject to local standard)
50m² (subject to local standard)
System wiring
2 core
Indication
360° visibility light pipe
Mounting
Surface mount CDBB300, FXN520 base
Compatibility
Conventional fire panels
Detetion Mode
Light scatter principle
Light scatter principle
Heat sensitive element
heat sensitive element
Operating voltage
15 to 30V dc
Max stand by current
30μA
Max Start up current
340μA
Max alarm current
25mA
Heat class
A2S
A2R
BS
CS
Alarm temperature
60°C
77°C
92°C
Environmental
Application
Indoor use IP 40
Temperature
-20°C to 60°C
-20°C to 45°C
-20°C to 60°C
-20°C to 60°C
-20°C to 75°C
Humidity
0 to 95% non condensing
EMC
CE marked
Construction
Material
PC/ABS
Colour
White
Dimensions
Excluding Base (Dia x H)
100mm x 43mm
Including Base (Dia x H)
100mm x 45mm
101mm x 55mm