Multisensor fire detector with integrated optical detector and heat detector. The optical measurement chamber is provided with a newly developed sensor technology, enabling the detection of open fires, smoldering fires and fires with high heat generation. Especially for open fires, the classical ionization technology implemented in ionization detectors is replaced by the new detection technology. The detector is capable of identifying the TF1 and TF6 test fires described in the EN 54-9:1982 specification.
The OTblue multisensor is an intelligent detector with time-related signal analysis, signal correlation of the sensor data, decentralized intelligence, automatic function self-test, CPU failure mode, automatic adaptation to environmental conditions, alarm and operating data memory, alarm indicator and soft-addressing.
The detector is provided with an integrated isolator and a parallel detector indicator can be connected.
Operating voltage : 9 ... 42 V DC
Quiescent current @ 19 V DC : approx. 50 μA
Alarm current w/o communication curtain : approx. 18 mA
Area to be monitored : max. 110 m²
Height to be monitored : max. 12 m
Air speed : 0 ... 25.4 m/s
Application temperature : -20 °C ... 50 °C
Storage temperature : -25 °C ... 75 °C
Type of protection : IP43 (with base + option)
Material : ABS
Air humidity : < 95 % (non-condensing)
Color : white, similar to RAL 9010
Weight : approx. 110 g
Detector specification : EN 54-7/-5 A2 /-17, CEA 4021
Dimensions : Ø: 117 mm H: 49 mm (62 mm incl. base)