[Notifier - THIẾT BỊ BÁO CHÁY NGOẠI VI LOẠI THƯỜNG] Đầu báo khói quang thường
Đầu báo khói quang và kết hợp quang/nhiệt System Sensor’s i³™ Series đại diện cho một bước tiến đáng kể của dòng báo cháy thường, kết hợp ba tính năng chính: dễ lắp đặt, thông minh, phát hiện nhanh chóng.
Dễ lắp đặt. Đầu báo i³ Series dễ dàng được lắp đặt nhờ thiết kế plug-in của nó. Điều này cho phép người cài đặt có thể lắp trước đế với phần đầu. The large wire-entry port and in-lineterminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of backbox mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i³ Series heads plug into the base with a simple Stop-Drop ’N Lock™ action.
Intelligence. Intelligence. i³ Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensa- tion and smoothing algorithms, to minimize nuisance alarms, are standard in the i³ Series. When connected to the 2W-MOD loop test/maintenance module, an SFP-2402/-2404 panel,SFP-5UD/10UD, or RP-2001/2002 two-wire i³ detectors are capable of generating a remote maintenance signal when they need cleaning. This signal is indicated by LEDs located at the module and at the panel. To read the sensitivity of i³ detectors, the SENS-RDR is a wireless device that displays sensitivity in terms of percent-per-foot obscuration.
Instant inspection. The i³ Series provides wide-angle red and green LED indicators for instant inspection of detector condi- tion. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The “EZ Walk” loop test feature is available on two-wire i³ Series detectors when con- nected to the 2W-MOD loop test/maintenance module. The “EZ Walk” feature verifies the initiating loop wiring by providing LED status indication at each detectorInstant inspection. The i³ Series provides wide-angle red and green LED indicators for instant inspection of detector condi- tion. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The “EZ Walk” loop test feature is available on two-wire i³ Series detectors when con- nected to the 2W-MOD loop test/maintenance module. The “EZ Walk” feature verifies the initiating loop wiring by providing LED status indication at each detector.
####
PHYSICAL SPECIFICATIONS
Operating Temperature Range: For models 2W-B and 4W-B:32°Fto 120°F (0°C to 49°C); for thermal models 2WT-B and4WT-B: 32°F to 100°F (0°C to 37.8°C).
Operating Humidity Range: 0% – 95% RH, non-condensing.
Thermal Sensor: 135°F (57.2°C) fixed (models 2WT-B,4WT-B).
Freeze Trouble: 41°F (5°C) (models 2WT-B and 4WT-B).Sensitivity: 2.5%/foot(0.762%/meter) nominal.
Input Terminals: Utilize 14 to 22 AWG wire.
Dimensions (including base): 5.3" (134.62 mm) diameter, 2.0" inches (50.8 mm) high.
Weight: 6.3 oz. (178.6 grams).
Mounting Options: 3.5" (88.9 mm) octagonal backbox; 4" (101.6 mm)octagonal backbox; single-gang backbox; 4" (101.6 mm) squarebackbox with a plaster ring; or direct mount to ceiling.
ELECTRICAL SPECIFICATIONS
Operating Voltage: 12/24 V non-polarized nominal; 8.5 V minimum; 35 V maximum.
Maximum Alarm Current” For two-wire models: 130 mAlim- ited by control panel; For four-wire models: 20 mA@ 12 V, 23 mA @ 24 V.
AlarmContact Ratings: For four-wire models: 0.5 A @ 30VAC/VDC; not applicable for two-wire models.
LED Modes | Green LED | Red LED | |
|
|
| |
Power Up | Blink every 10 sec- | Blink every 10 sec- | |
onds | onds | ||
| |||
|
|
| |
Normal (Standby) | Blink every 5 sec- | OFF | |
onds | |||
|
|
| |
Out of Sensitivity | OFF | Blink every 5 sec- | |
onds | |||
|
| ||
|
|
| |
Freeze Trouble | OFF | Blink every 10 sec- | |
onds | |||
|
| ||
|
|
| |
Alarm | OFF | Solid ON | |
|
|
| |
Power Up Sequence for LED Indication | |||
|
| ||
Condition | Duration | ||
|
| ||
Initial LED Status Indication | 80 Seconds | ||
|
|
|